Temperature-Logger
for monitoring production and server-rooms as well as cooling chambers
according to assignation of frozen food 92/1/EWG
Certificate of calibration (not available at
..40KH-GOF)
measuring points: -20°C/0°C/+60°C (at ..40K) or
-20°C/0°C/+70°C (at ..40KH)!
Specifications: |
| measuring ranges: | EASY-LOG 40K: | -25.0°C to 60.0°C |
| EASY-LOG 40KH: | -50.0°C to 150.0°C | |
| EASY-LOG 40KH-E300: | -50.0°C to 300.0°C | |
| EASY-LOG 40KH-E600: | -50.0°C to 600.0°C | |
| EASY-LOG 40KH-GOF: | -50.0°C to 200.0°C | |
| resolution of display and memory: | 0.1°C or 1°C (corresponding to type) | |
| working temperature electronics: | -25°C to 60°C | |
|
accuracy:
(at nominal temperature = +25°C) |
EASY-LOG 40K: | +0.5°C |
| EASY-LOG 40KH: | + 0.5°C | |
| EASY-LOG 40KH-E300: | 0.5°C +0.2% of meas. value | |
| EASY-LOG 40KH-E600: | 1°C +0.2% of meas. value | |
| EASY-LOG 40KH-GOF: | 0.5°C +0.2% of meas. value | |
| sensor: Pt1000 (2-wire) | design 40K | sensor tube made of plastic, diameter
7mm, approx. 30mm long, fixly mounted at the device |
| (remark: at certificate stainless steel tube, diameter 5mm, approx. 60mm long) |
||
| design 40KH | sensor tube made of
stainless steel, diameter 5mm, approx. 50mm long, approx. 1m silicon cable, cable with anti-buckling glanding to housing. |
|
| design 40KH-E300 | sensor tube made of
stainless steel, diameter 3mm, approx. 100mm long, sleeve diameter 5 x 50mm, approx. 1m glass silk cable, cable with anti-buckling glanding to housing |
|
| design 40KH-E600 | sensor tube made of
stainless steel, diameter 3mm, approx. 100mm long, sleeve 5 x 50mm, flexible coating-element, approx. 1m silicone cable, cable with anti-buckling glanding to housing |
|
| design 40KH-GOF | self-adhesive surface
temperature probe with moulded silicone design (type GOF 115 Pt1000) approx. 2m PFA-insulated cable, cable with anti-buckling glanding to housing. |
|
| special design types upon request! | ||
| display: | 10mm high LCD-display |
| recording temperature: | 2 sec. to 5h (freely programmable via software GSOFT 40K) |
| storage capacity: | 48,000 measuring values |
| recording time: | 500 days (if recording interval is 15min.) |
| battery service life: | approx 6 years (at 15min.) double battery capacity against upcharge available! |
| working temperature (electronic): | -25°C to +60°C |
| storage temperature: | -30°C to +70°C |
| interface: | EASY-BUS-interface, 3-pin
mini-integral plug, needed connection cable EBSK01 not included in delivery |
| Remark: with an according interface converter you can connect 120 logger to one RS232-interface without any problems |
|
| housing: | 48.5 x 48.5 x 35.5mm (H x W x D), sensor and plug not included IP 65 |
| noise immunity (EMC): | the EASYLOG have been
manufactured in accordance with the regulations concerning EMC (2004/108/EG) The device meets EN50081-1 and EN50082-1 additional error: <0.5% |
options (against upcharges): |
| DBK: | double battery capacity | recommended for fast measuring series |
| Alarm: | additional alarm-output: | open-collector output via 4-pole miniature
panel plug (IP65), 1m cable incl., max. switching power: 28V, 50mA |
| AFK: | removable probe-cable: | 4-pole (IP65) miniature
panel plug assembling of the corresponding connection socket to the corresponding temperature probe incl. |
| SMB: | extra measuring range: | freely selectable between -200°C
to +600°C The essential probe-adjustment is not included in this price. |
| Remark: At a measuring span <400°C (e.g. +200°C) a
resolution of 0.1°C is possible.Wider ranges have got a resolution of 1°C. |
(c) 1999-2010 GSG Geologie-Service GmbH, Wuerzburg -
www.geologie-service.com
Tel. +49/(0)931 30 40 8-0; FAX: +49/(0)931 99105-90
- All rights reserved -