measuring principle: |
magnetic-inductive |
|
measuring range: |
MID1-008: |
0.05 to 1l/min. |
|
MID1-015: |
0.5 to 10l/min. |
|
MID1-025: |
3 to 60l/min. |
|
accuracy: |
+2.5% of meas. value or +0.5% of final value
(higher value) - after 2 s setting time |
|
working pressure: |
max. 10 bar |
|
output signal: |
0 to 400 Hz, NPN open collector |
|
optional: .../EFFI
|
4 to 20 mA (3-wire) |
|
optional: .../EFFU |
0 to 10 V (3-wire) |
|
auxiliary energy: |
12 to
24 V DC |
|
with option EFF..: |
18 to 24 V DC +10 % |
|
current consumption: |
max. 120mA (closed current, without load) |
|
electrical connection: |
4-pole locking plug M12 x 1 |
|
working temperature: |
0°C to +60°C |
|
protection class: |
IP 67 |
|
mech. connection: |
MID1-008: |
R1/4" (= 0.635 cm), female thread |
|
MID1-015: |
R1/2" (= 1.27 cm), female thread |
|
MID1-025: |
R1" (= 2.54 cm), female thread |
|
mounting postition: |
any |
|
dimensions: |
|
contacting media: |
stainless steel 1.4404, PPS and FKM |
|
dimensions: |
MID1-008: |
85 x 46 x 89 mm (L x W x H) |
|
MID1-015: |
95 x 46 x 93 mm (L x W x H) |
|
MID1-025: |
110 x 48 x 102 mm (L x W x H) |
|
(height at option EFF...: + 25 mm) |