isolating signal converter
| properties:
Isolating signal converter for application in zone 0 or zone 20 (permanent
explosion risk)
|
![]() |
ST 500-Ex-ia-10-0
(230V AC)
|
ST 500-Ex-ia-10-5
(10 bis 30V DC/AC)
|
specifications: |
|
measuring range: (selectable) |
current input: | 0 to 20 mA or 4 to 20 mA |
| (Ri = 25 Ω, max. 100 mA overload) | ||
| voltage input: | 0 to 10 V or 2 to 10 V | |
| (Ri = ~ 40 kΩ, max. 100 V overload) | ||
| span: | approx. +20% adjustable | |
| transmitter supply: | approx. 20 V DC, Ri = approx. 300 Ω | |
| output signal: | 0 to 20 mA, 4 to 20 mA, 0 to 10 V or 2 to 10 V (selectable via DIP switch) | |
| max. load: burden < 1k Ω (at mA), 15 mA (at V) | ||
| basic accuracy: | <0.3 % of measuring range | |
| temperature coefficient: | <0.01 %/K | |
| repeat accuracy: | <0.1 % of measuring range | |
| rise time: | T90 = < 100ms | |
| power supply: | ... to 0 | 85 to 253V AC/ |
| ... to 5 | 10 to 30V DC/AC | |
| power consumption: | max. 3.5 VA | |
| isolation voltage: | 500 V AC, according to VDE 0110 Gr. 2 | |
| between input/output/supply voltage | ||
| test voltage: | 4 kV DC between input/output/supply voltage | |
| working temperature: | -10°C to +55°C | |
| electrical connection: | screw-type terminals with pressure plates, max. 2.5 mm2 | |
| dimensions: | 22.5 x 75 x 110mm (W x D x H) | |
| protection: | IP 30 (case), IP 20 (terminals) | |
| Ex-certification: | TUEV 03 ATEX 2283, II (1) GD [EEx ia] IIC | |
| connection data: | Uo = 25.2 V, Io = 95 mA, Po = 600 mW, | |
| Co = 107 nF (ia/IIC), 820 nF (ia/IIB), | ||
| Lo = 2.3 mH (ia/IIC), 14 mH (ia/IIB), | ||
| Ci, Li = negligible | ||
| The intrinsically safe mesuring input is
reliably electrically
isolated from all non-intrinsically safe circuits up to a peak values of 375 V. |
||