Freely scaleable temperature transducer
General information:
The new
generation of our temperature transmitters brings more flexibility thanks to
state to the art microprocessor technology.
|
Design 1
for direct screw connection
|
Design 2
for high temperatures
|
Design 3
indoor/outdoor probe
|
Design 4
Duct probe
|
GTMU-MP1
|
Design 1 |
GTMU-MP2
|
Design 2 |
GTMU-MP3
|
Design 3 |
GTMU-MP4
|
Design 4 |
SPECIFICATION: |
|
Measuring range: |
-50 to +
400°C, freely scaleable The probe length FL has to be chosen long
enough that |
Accuracy: |
(At
nominal temperature = 25°C) Display - tamperature: +0.4% of meas. value +0.2 °C Output signal: + 0.2% FS |
Measuring probe: | Pt1000, 2-wire |
Output signal: |
Standard: 4 - 20 mA (2-wire),
freely scaleable Option: 0-1V, 0-10 V (further output signals upon request!) |
Auxiliary energy: | Uv = 12 ... 30 V DC (at 0-10 V: Uv = 18 ... 30 V DC) |
Reverse voltage protection: | 50 V, permanently |
Permissible impedance: | (at 4-20 mA) RA (Ohm) = Uv (V) - 12 / 0.02 A) |
Permissible load: | (at 0-1(10)V) RL (Ohm) > 3000 Ohm |
Working temperature electronics: | 0 to + 70 °C |
Storage temperature: | -25 to +70 °C |
Housing: | ABS (IP65) |
Mounting: | 4 housing holes for wall mountings or by means of plastic tube clamps for duct mounting |
Electric connection: | elbow-type plug acc. to DIN 43650 (IP 65) |
Thread sizes "G": |
Standard:
G 1/2" (= 1,27 cm) Option: G 1/4" (= 0,635 cm), G 3/8" (=0,9525 cm), G 3/4" (= 1,905 cm), M10, M12, M14, M16 |
Tube: |
stainless steel Diameter "D": 3, 4, 5, 6 or 8 mm Tube length "FL": Standardized length p.r.t. various designs optionally any length possible The probe length FL has to be chosen long enough that the allowable temperature of the case and the electronics of 70°C is not exceeded! |
Functions: |
min-/max-value memory, offset and slope digital adjustable, output signal freely scaleable (without tools) |
Examples for ordering: |
If no additional data is added to the design type, the
probe will be manufactured with standard dimensions.
If different dimensions are required, they have to be specified.
GTMU, design 1,
GTMU, design 3, FL=100mm, D=4mm
Options: |
|
-AV... |
further output signal (0-1V or 0-10V, further output signals upon request) |
-LACK | encapsulated PC board (for outdoor application, i.e. applications, where condensation is possible) |
- FL | Longer tube, each startet further 100mm |
-HL | Longer collar tube, each startet further 100mm |
-D | other probe diameter (without surcharge) |
-G | other thread (without surcharge) |
Clamping ring screw connection (upon request) |